Troubleshooting
03/07/03
4-9
Possible Cause Checks Corrective Action
Leak detector did not open. Check the settings of switches
SW1-3 and SW1-4 to
determine the selected delay
time.
Leak in supply line or piping.
Select a longer delay time if
needed.
Replace defective leak
detector if it does not open.
Repair leak.
Shear valve tripped. Try to determine cause (loose
mounting to island, cabinet
had been hit, etc.)
Reset, or if necessary, replace
shear valve if it is tripped.
Correct cause of valve
tripping.
Defective submersible motor. Repair or replace motor.