Maintenance instructions
QS4 Technical Reference Manual 6.5
Table 6-6: General CPU pseudo points
LCD Indication Event Type Definition
Startup Response Monitor Monitor point that goes active on system startup or
after restart.
First Alarm Alarm Occurs anytime that the system goes into alarm
for the first time.
First Supervisory Supervisory
Occurs anytime that the system goes into
supervisory for the first time.
First Trouble Trouble Occurs anytime that the system goes into a
trouble for the first time.
First Monitor Monitor
Occurs anytime that the system goes into a
monitor condition for the first time.
Evacuation
Drill Monitor This point will go active anytime drill is pressed.
Alarm Silence Monitor
This point will go active anytime alarm silence is
pressed.
Two Stage Expiration
Reset Monitor This point goes active anytime reset is pressed.
Reset Phase 1 Monitor Active during the power down phase of reset.
Reset Phase 2 Monitor Active during the retard phase of reset.
Reset Phase 3 Monitor Active during the restoration phase of reset.
First Disable Trouble Activated the first time an item is disabled from the
front menu.
First Test Trouble
Activated the first time a service group is started
from the front menus.
Two Stage Timer Started
User Trouble Trouble Triggered by custom programming.