Operating instructions
QS4 Technical Reference Manual 3.3
Tasks that do not require you to log in
What is it you want to do This is how you do it
Identify points that are disabled
1. Press Status.
2. Choose Disabled Pts.
3. Press DEL to backspace the cursor then enter the panel
number.
4. Choose Display to view the list on the CPU/Display unit.
— or —
Choose Printer to print the list.
Identify output devices that are
turned on
1. Press Status.
2. Choose Outputs
3. Press DEL to backspace the cursor then enter the panel
number.
4. Choose Display to view the list on the CPU/Display unit.
— or —
Choose Printer to print the list.
Verify power supply voltage levels
1. Press Status.
2. Choose Internal
3. Press Enter.
4. Choose Display to view the list on the CPU/Display unit.
— or —
Choose Printer to print the list.
Get a list of smoke detectors that
require servicing (DIRTY attribute
greater than 80%)
1. Press Menu.
2. Choose Reports > Maintenance > Dirty>80%.
3 Enter the panel number.
4. Choose Display to view the list on the CPU/Display unit.
— or —
Choose Printer to print the list.
Technical Manuals Online! - http://www.tech-man.com