EasyManua.ls Logo

GE 239

GE 239
158 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GE Multilin 239 Motor Protection Relay 2-11
2 INSTALLATION 2 INSTALLATION
2
h) ANALOG OUTPUT (OPTION) (18/19/20)
Terminals 18-20 of the 239 are available for a single analog current output of one parameter. Verify
that the Analog Output option is installed by noting that the product identification label on back of the
relay includes -AN in the order code. The choice of output and current range is selected in
6
6(783?$1$/2*287387?$1$/2*2873877<3(5$1*(
. Use the TYPE message to select one of the fol-
lowing for output: phase CT (secondary) amps, % motor full load current (FLC), thermal capacity
used (100% = motor tripped), RTD1 temperature, RTD2 temperature, or RTD3 temperature. The
RANGE message selects the output current as: 0-1 mA, 0-20 mA or 4-20 mA. Range assignment is
shown below in Table 2–4: ANALOG OUTPUT RANGE ASSIGNMENT.
This output is a current source suitable for connection to a remote meter, chart recorder, programma-
ble controller, or computer load. Use the 4-20 mA with a programmable controller that has a current
input. If only a voltage input is available use a scaling resistor at the PLC terminals to scale the cur-
rent to the equivalent voltage and select the 0 to 20 mA output. For example, install a 500 resistor
across the terminals of a 0 to 10 V input to make the 0 to 20 mA output correspond to 0 to 10V (R =
V/I = 10 V / 0.02 A = 500 ). When the GE Multilin TCS2 thermal capacity meter is connected to the
terminals, select the 0 to 1 mA range. Current levels are not affected by the total lead and load resis-
tance which must not exceed 600 for 0-20 mA and 4-20mA range and 2400 for 0-1mA range.
For readings greater than full scale the output will saturate at 21 mA (0-20/4-20 range) or 1.1 mA (0-
1 range). This analog output is isolated. Since both output terminals 18 and 19 are floating, the con-
nection of the analog output to a process input will not introduce a ground loop. Part of the system
should be grounded for safety, typically at the programmable controller. For floating loads, such as a
meter, ground terminal 19 externally. Terminal 20 is internally grounded and may be used as a shield
ground if required. Ground the shield at one end only to prevent ground loop noise.
i) SERIAL PORT (15/16/17)
A serial port provides communication capabilities between the 239 and a remote computer, PLC or
distributed control system (DCS). Up to thirty-two 239 relays can be daisy chained together with 24
AWG stranded, shielded, twisted pair wire on a single communication channel. Suitable wire should
have a characteristic impedance of 120 such as Belden #9841. These wires should be routed
away from high power AC lines and other sources of electrical noise. The total length of the commu-
nications wiring should not exceed 4000 feet for reliable operation. Correct polarity is essential for
the communications port to operate. Terminal 15 (485 A+) of every 239 in a serial communication link
must be connected together. Similarly, terminal 16 (485 B-) of every 239 must also be connected
together. These polarities are specified for a 0 logic and should match the polarity of the master
Table 24: ANALOG OUTPUT RANGE ASSIGNMENT
SELECTED OUTPUT
PROGRAMMED RANGE
0-1 mA 0-20 mA 4-20 mA
0 mA 1 mA 0 mA 20 mA 4 mA 20 mA
Average Phase Current 0 A 1A/5A* 0 A 1A/5A* 0A 1A/5A*
Motor Full Load% 0%200%0%200%0%200%
Thermal Capacity 0% 100% 0% 100% 0% 100%
RTD 1-3 Temperature 0°C180°C0°C180°C0°C180°C
Forced Output 0% 100% 0% 100% 0% 100%
* 1 Amp CT secondary = 1 A, 5 Amp CT secondary = 5 A

Related product manuals