EasyManua.ls Logo

GE 239

GE 239
158 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-12 239 Motor Protection Relay GE Multilin
4 PROGRAMMING 4 PROGRAMMING
4
above. In between these two extremes there is a linear relationship; the 239 thermal model cov-
ers the entire range of motor temperatures: coldcool—warm—hot. The steady state value of
thermal capacity used for any phase current level can be calculated as:
For example, if LRT Hot = 7.0 s, LRT Cold = 10.0 s, FLC = 100 A, and the actual motor current is
80 A, then the steady state thermal capacity value will be:
DISABLE STARTS: In some applications start protection may not be required. Therefore, by set-
ting this setpoint to
<(6, the start protection on the 239 can be defeated. If the setpoint is set to
<(6, the 239 will go directly into run condition and overload curves will be employed to protect the
connected load.
This setpoint can also be used in conjunction with a switch input. If the
',6$%/(67$576 setpoint is
programmed to
<(6 and 237,216:,7&+  )81&7,21 setpoint described on page 4–33 is assigned
to
',6$%/(67$576, the 239 start protection will be defeated if the respective switch input is closed.
The
',6$%/(67 $576 setpoint must be programmed to <(6 for the feature to work via the switch
inputs.
Thermal Capacity Used
Actual Current
FLC Setpoint
--------------------------------------
100% HOT/COLD CURVE RATIO
()×
=
Thermal Capacity Used
Actual Current
FLC Setpoint
--------------------------------------
100% HOT/COLD CURVE RATIO
()×
=
80
100
----------
100%
7.0
10.0
-----------
100%×




×
=
20%
=

Related product manuals