4-16 239 Motor Protection Relay GE Multilin
4 PROGRAMMING 4 PROGRAMMING
4
MESSAGE
▼
MESSAGE
▲
| MECHANICAL JAM
|
MECHANICAL JAM
FUNCTION: OFF
MECHANICAL JAM
PICKUP
≥
2.0 x FLC
MECHANICAL JAM
DELAY: 2 s
| UNDERCURRENT
|
Range: OFF, TRIP, ALARM,
AUXILIARY, TRIP&AUX
Range: 0.1 to 10.0
Step 0.1 x FLC
Range: 0 to 250; Step: 1 s.
UNDERCURRENT
FUNCTION: OFF
| UNBALANCE
|
INHIBIT ON START
FOR: UNLIMITED s
Range: OFF, ALARM, AUXILIARY,
TRIP, ALARM & AUX, TRIP & AUX
Range: 0 to 250; Step: 1 s.
Range: 5 to 100; Step: 1%
UNDERCURRENT
PICKUP
≤
50% FLC
UNDERCURRENT
DELAY: 2 s
Range: 5 to 100; Step: 1%
PHASE UNBALANCE
TRIP: ON
PHASE UNBALANCE
TRIP PICKUP
≥
20 %
PHASE UNBALANCE
TRIP DELAY: 2 s
Range: ON, OFF
Range: 0 to 60; Step: 1 s
Range: 0 to 6000, UNLIMITED
Step: 1 s
SEE NEXT PAGESEE NEXT PAGE
MESSAGE
▲
MESSAGE
▲
MESSAGE
▼
MESSAGE
▼
PHASE UNBALANCE
ALARM: ON
PHASE UNBALANCE
ALARM PICKUP
≤
5 %
SEE PREVIOUS PAGESEE PREVIOUS PAGE
Range: ON, OFF
Range: 5 to 100
Step: 1%
| HOT MOTOR
|
THERMAL CAPACITY
USED ALARM
≥
OFF %
MESSAGE
▲
MESSAGE
▼
Range: 0 to 100; Step: 1%