EasyManua.ls Logo

GE 239

GE 239
158 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GE Multilin 239 Motor Protection Relay 5-3
5 MONITORING 5 MONITORING
5
] LAST TRIP DATA
]
SEE PREVIOUS PAGE
CAUSE OF LAST TRIP:
NO TRIP
] SWITCH STATUS
]
SW. 1 ACCESS
SWITCH STATE: OPEN
SW.2 EMERG RESTART
SWITCH STATE: OPEN
SW.3 EXTERNAL RESET
SWITCH STATE: OPEN
OPTION SWITCH 1
SWITCH STATE: OPEN
MESSAGE
4
MESSAGE
4
MESSAGE
3
MESSAGE
3
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Range: NO TRIP, OVERLOAD, SHORT CIRCUIT, MECHANICAL
JAM, UNBALANCE, GROUND FAULT, STATOR RTD, BEARING
RTD, UNDERCURRENT, THERMISTOR, COMPUTER TRIP,
PARAMETERS NOT SET, OPTION SWITCH 1, OPTION SWITCH 2
A= 0 B= 0
C= 0 AMPS
GROUND CURRENT=
0.0 A
CURRENT UNBALANCE
U/B= 0%
STATOR RTD 1 TEMP:
130°C
BEARING RTD 2
NO RTD
BEARING RTD 3
NO RTD
SETPOINTS GROUP
IN USE: MAIN
2nd LAST TRIP:
NO TRIP
3rd LAST TRIP:
NO TRIP
4th LAST TRIP:
NO TRIP
5th LAST TRIP:
NO TRIP
OPTION SWITCH 2
SWITCH STATE: OPEN
MAIN SETPOINTS GROUP
CURRENTLY IN USE
Range: 0 to 10000
Range: 0 to 1000
Range: 0 to 100
Range: –40 to +200 °C
–40 to +400 °F
Range: –40 to +200 °C
–40 to +400 °F
Range: –40 to +200 °C
–40 to +400 °F
Range: MAIN, 2nd, 3rd, 4th
Range: Same as CAUSE OF
LAST TRIP above
Range: OPEN, CLOSED
Range: OPEN, CLOSED
Range: OPEN, CLOSED
Range: OPEN, CLOSED
Range: OPEN, CLOSED
Range: OPEN, CLOSED
] MOTOR STATISTICS
]
MOTOR MAX STARTING
CURRENT = 0 A
RUNNING TIME:
0.0 h
MESSAGE
4
MESSAGE
3
Range: 0 to 10000 A
Range: 0 to 429496729.6 hrs
SEE NEXT PAGE

Related product manuals