EasyManua.ls Logo

GE 735

GE 735
110 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A-2 735/737 Feeder Protection Relay
GE Power Management
A.2 FEEDER DEDICATED TO A TRANSFORMER APPENDIX A
A
A.2 FEEDER DEDICATED TO A TRANSFORMER A.2.1 CHARACTERISTICS
Feeder Dedicated to a Transformer:
From short circuit study:
Maximum load current = = 138 A
Maximum transformer inrush = = 1255 A
•3Φ fault in high voltage cable = 1760 A
Ground fault in high voltage cable = 2100 A
•3Φ fault in 600 V cable = 20600 A
A.2.2 PHASE TIMED O/C PICKUP
The phase time overcurrent pickup is approximately equal to 1.2 to 1.5 times the maximum current, for example: 1.3 × 138
A = 179.4 A. Thus,
Phase Pickup dial setting = = 120%
From time coordination curves established in the coordination study, with a minimum coordination between devices of 0.3
seconds (normally between 0.2 and 0.5 seconds), determine curve shape and time multiplier.
Phase Curve Shape dial setting = VERY INVERSE
Phase Time Multiplier dial setting = 3
A.2.3 PHASE INSTANTANEOUS
It is desirable to operate this protection for a fault on the 600V bus.
Fault current at 13.8 kV = = 895 Amps
This current is less than the maximum possible transformer inrush current of 1255 A. Thus this value cannot be used.
Instead set instantaneous pickup at 120% of inrush level.
Instantaneous pickup current level = 1.2 × 1255 = 1506 A
Phase Instantaneous dial setting = 1506 A / 150 A 10
3300 kVA
3 13.8 kV×
----------------------------------
2500 kVA
3 13.8 kV×
----------------------------------
12×
179.4 A
150 A
---------------------
100×
20600 A 600 A×
13800 A
------- ----------------------- --------------- 895 A=

Table of Contents

Related product manuals