735/737 Feeder Protection Relay 3-17
3 SETUP AND OPERATION 3.6 SETUP EXAMPLE
3
Slave address: 10
Baud rate: 9600
For a baud rate of 9600, 2=on, 1=off. Choose the combination of numbers that adds up to the required slave address: 10 =
2 (4=on) + 8 (6=on), (3=off, 5=off, 7=off). Disable communications test mode for normal operations (Test 8=off). The switch
settings are:
SWITCH POSITION SETTING
1 OFF 9600 baud
2ON
3 OFF Address 10
4ON
5OFF
6ON
7OFF
8 OFF Test OFF