GE Power Management
735/737 Feeder Protection Relay 4-11
4 MODBUS COMMUNICATIONS 4.3 MEMORY MAP
4
SYSTEM
CONFIG
002A Phase Pickup dial settin
g
1 to 19 1 dial F108 ---
002B Phase Curve Shape dial settin
g
1 to 10 1 dial F107 ---
002C Phase Time Multiplier dial settin
g
1 to 10 1 dial F112 ---
002D Phase Instantaneous dial settin
g
1 to 10 1 dial F109 ---
002E Ground Pickup dial settin
g
1 to 19 1 dial F110 ---
002F Ground Curve Shape dial settin
g
1 to 10 1 dial F107 ---
0030 Ground Time Multiplier dial settin
g
1 to 10 1 dial F112 ---
0031 Ground Instantaneous dial settin
g
1 to 10 1 dial F111 ---
0032 Comm DIP switch settin
g
--- --- --- F102 ---
0033 Curve shift switch settin
g
--- --- --- F114 ---
0034 Reset switch status 0-1 1 1=on F1 ---
0035 Not used --- --- --- --- ---
↓↓
004F Not used --- --- --- --- ---
SETPOINTS
DIAL
SETTINGS FOR
SIMULATION
AND TEST I/O
0050 Phase Pickup dial (Remote) 1 to 19 1 dial F108 0
0051 Phase Curve Shape dial (Remote) 1 to 5 1 dial F104 0
0052 Phase Time Multiplier dial (Remote) 1 to 10 1 dial F112 0
0053 Phase Instantaneous dial (Remote) 1 to 10 1 dial F109 0
0054 Ground Pickup dial (Remote) 1 to 19 1 dial F110 0
0055 Ground Curve Shape dial (Remote) 1 to 5 1 dial F104 0
0056 Ground Time Multiplier dial (Remote) 1 to 10 1 dial F112 0
0057 Ground Instantaneous dial (Remote) 1 to 10 1 dial F111 0
0058 Phase A current (Simulation) 0 to 2000 1 % CT F1 0
0059 Phase B current (Simulation) 0 to 2000 1 % CT F1 0
005A Phase C current (Simulation) 0 to 2000 1 % CT F1 0
005B Ground current (Simulation) 0 to 2000 1 % CT F1 0
005C Output relays (Test - I/O) Bits --- --- F103 0
005D LED (Test - I/O) Bits --- --- F105 0
005E Bar
g
raph (Test - I/O) Bits --- --- F106 0
005F Curve shift switch Bits --- --- F114 0
CUSTOM
SCHEME
0060 Curve Shape 0 to 2 1 --- F116 0
0061 Block Instantaneous 0 to 180 1 0=OFF F117 OFF
0062 Aux Trip Relay 0 to 2 1 --- F118 0
COMMANDS 0063 Reset 0 to 1 1 1=reset F1 0
0064 Clear Last Trips 0 to 1 1 1=clear F1 0
0065 Not used --- --- --- --- ---
↓↓
006F Not used --- --- --- --- ---
Table 4–1: 735/737 MODBUS MEMORY MAP (Sheet 2 of 2)
GROUP ADDR DESCRIPTION RANGE STEP UNITS FOR-
MAT
FACTORY
DEFAULT