80
Advent Commercial Fire System
xx117 Account Number 2 (page 18) 00000000 1_____________, 3_____________, 5_____________, 7_____________,
2_____________, 4_____________, 6_____________, 8_____________
xx118 Default Keyfob Schedule Arming Level
(page 23) 3
1_____________, 3_____________, 5_____________, 7_____________,
2_____________, 4_____________, 6_____________, 8_____________
xx120 Default Keyswitch Arming Level (page 23) 3 1_____________, 3_____________, 5_____________, 7_____________,
2_____________, 4_____________, 6_____________, 8_____________
17001 System Date (page 45) 1/1/00
17002 System Time (page 45) 12:00:00
17003 System Day of Week (page 45) Saturday
17004 System Report Time (STIME) (page 46)
Random
17006-17111
17118
General Input Response Times (page 39)
32 sec
I/O 1__________, I/O 3__________, I/O 5__________, I/O 7__________
I/O 2__________, I/O 4__________, I/O 6__________
17012-17017
17119-17120
Expansion Input Response Times (page 39)
32 sec
1_____________, 3_____________, 5_____________, 7_____________,
2_____________, 4_____________, 6_____________, 8_____________
17018 Max Ring Cycle Time (page 31) 67 ms
17019 Minimum Ringlet Burst Duration (page 32)
400 ms
17020 Maximum Ringlet Burst Duration (page 32)
2500 ms
17021 Minimum Pause Between Ringlets (page 32) 0
17022 Maximum Pause Between Ringlets (page 32) 0
17023 Minimum Pause Between Rings (page 33)
2000 ms
17024 Maximum Pause Between Rings (page 32)
4500 ms
17025 Minimum Time Between Ring-Pause-Ring
(page 35) 10 sec
17026 Max Time Between Ring-Pause-Ring
(page 35) 30 sec
17027 On Hook Hang Up Time (page 34) 4 sec
17028 Local Phone Connect Time (page 33) 2 sec
17029 Local Phone Answer Time (page 34) 8 sec
17030 Max Delay Between Phone Panic Sequence
(page 33) 2 sec
17031 DTMF On Time (page 32) 30 ms
17032 DTMF Off Time (page 32) 50 ms
17034 Phone Test Interval (page 29) 1 day -
Commercial, 7 days - Home Navigator
17035 Touchpad Redirect Reset Time (page 17) 10
sec
17036 AC Stable Time (page 48) 8 sec
17037 Low Battery Trip Voltage (page 47) 10.6V
17038 Battery Restored Voltage (page 47) 11.6V
17039 Battery Voltage Shutdown is Started (page 47)
9.4V
17040 Battery Voltage Shutdown is Canceled
(page 48) 10.4V
17041 Hours to Delay Before Reporting AC Failure
(page 47) 6 hrs
17043 Percent Full History Buffer Reports (page 46)
80 percent
Table A.13 Item Numbers Index and Record (Continued)
Item
Number
Setting Reference and Default Setting