81
Advent Commercial Fire System
17044 Percent Full Report Buffer Reports (page 46)
80 percent
17046-17048 Siren Cadence (page 44) Medical alternate
modulated, Police steady, Auxiliary fast
modulated
Medical_______, Police_________, Auxiliary_______
17049-17050 RF Supervisory Times (page 45) A 4 hrs,
B 24 hrs
A_____________, B_____________
17051 Smoke Loop Reset Time (page 38) 3 seconds
17052 Answer Phone after XX Rings (page 34) 12
Rings
17053 Cancel Ring-Pause-Ring After XX Rings
(page 35) 3 rings
17054 Minimum Cycles in a Valid Ring (page 32) 2
cycles
17055 Number of Ringlets Needed for a Valid Ring
(page 32) 1 burst
17056 Local Phone Connect Sequence (page 33) #*
17057 Phone Device Override Sequence (page 33)
**##
17058 System Pager ID (page 29) 0
17060-17061 On Premises Pager IDs (page 48) 0000000 1_____________, 2_____________
17062 System Strobe Light Type (page 44) Amesco
17063-17068 General Purpose I/O Direction (page 39) 0
(input)
1_____________, 3_____________, 5_____________,
2_____________, 4_____________, 6_____________
17069 No Phone Line Attached (page 28) Off
17070 Enable Daylight Savings (page 47) On
17072 Enable RF Jam Detect (page 46) On
17073 Battery Test Interval (page 46) 4 hours
17074 High Rise Installation (page 46) Off
17075 Enable Long Range Radio (page 46) Off
17076 Commercial or Residential Installation
(page 46) Home Navigator Off, Commercial
On
17078 Detect Receiver Failure (page 45) On
17079 Alarm Messages Played at High Volume
(page 43) On
17080 Enable Local Phone Police Alarm (page 34)
Off
17081 Enable Local Phone Auxiliary Alarm
(page 34) Off
17082 Enable Local Phone Fire Alarm (page 34) Off
17083 Play Evacuation Message During Fire Alarms
(page 43) On
17084 First Disarm Silences Fire Alarm and Second
Disarm Cancels the Alarm (page 44)
Commercial Fire On, Commercial Burglary
Off
17085 Enable Local Phone Access in Partition/Area 1
(page 33) Off
17086 Enable Remote Phone Access (page 34) On
17087 Enable Remote Phone Ring Count (page 34)
On
Table A.13 Item Numbers Index and Record (Continued)
Item
Number
Setting Reference and Default Setting