AP-23 No-Flow Function
Option: Function:
Common actions for Low Power Detection and Low Speed Detection (Individual selections not possible).
[0] * Off
[1] Sleep Mode
[2] Warning Messages in the keypad display (if mounted) and/or signal via a relay or a digital output.
[3] Alarm The frequency converter trips and motor stays stopped until reset.
AP-24 No-Flow Delay
Range: Function:
10 s* [1 - 600 s] Set the time Low Power/Low Speed must stay detected to activate signal for actions. If detection disap-
pears before run out of the timer, the timer will be reset.
AP-26 Dry Pump Function
Option: Function:
Low Power Detection must be Enabled (par. AP-21 Low Power Detection) and commissioned (using either
par. AP-3#, No Flow Power Tuning, or par. AP-20 Low Power Auto Set-up) in order to use Dry Pump De-
tection.
[0] * Off
[1] Warning Messages in the keypad display (if mounted) and/or signal via a relay or a digital output.
[2] Alarm The frequency converter trips and motor stays stopped until reset.
AP-40 Minimum Run Time
Range: Function:
10 s* [0 - 600 s] Set the desired minimum running time for the motor after a start command (digital input or Bus) before
entering Sleep Mode.
AP-41 Minimum Sleep Time
Range: Function:
10 s* [0 - 600 s] Set the desired Minimum Time for staying in Sleep Mode. This will override any wake up conditions.
AP-42 Wake-up Speed [RPM]
Range: Function:
0 RPM* [par. F-18 - par. F-17 RPM] To be used if par. K-02 Motor Speed Unit has been set for RPM (parameter not visible if Hz selected). Only
to be used if par. H-40 Configuration Mode is set for Open Loop and speed reference is applied by an
external controller.
Set the reference speed at which the Sleep Mode should be cancelled.
AP-60 Broken Belt Function
Option: Function:
Selects the action to be performed if the Broken Belt condition is detected
[0] * Off
[1] Warning
[2] Trip
AP-61 Broken Belt Torque
Range: Function:
10 %* [0 - 100 %] Sets the broken belt torque as a percentage of the rated motor torque.
AF-600 FP High Power Operating Instructions