EasyManua.ls Logo

GE AF-650 GP - General Module Removal Instructions; AC Line Input Fuse Removal

GE AF-650 GP
215 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
H-96 KTY Thermistor Input
Option: Function:
Selecting analog input terminal 54 to be used as KTY sensor input. Terminal 54 cannot be selected as KTY
source if otherwise used as reference (see par. F-01 Frequency Setting 1 to par. C-34 Frequency Command
3).
NB!
Connection of KTY-sensor between term. 54 and 55 (GND). See picture in section KTY Sensor Connec-
tion.
[0] * None
[2] Analog Input 54
H-97 KTY Threshold level
Range: Function:
80 °C* [-40 - 140 °C] Select the KTY sensor threshold level for motor thermal protection.
AF-650 GP Programming Guide
99
3

Table of Contents

Other manuals for GE AF-650 GP