3.11 DN-## CAN Fieldbus
Parameter group related to Field Installed DeviceNet Network Communications Option Module.
3.11.1 DN-0# Common Settings
Parameters to configure the commom settings for DeviceNet.
DN-00 DeviceNet Protocol
Option: Function:
[0] CANopen
[1] * DeviceNet View the active CAN protocol.
NB!
The options depend on installed option.
DN-01 Baud Rate Select
Select the network transmission speed. The selection must correspond to the transmission speed of the master and the other network nodes.
Option: Function:
[16] 10 Kbps
[17] 20 Kbps
[18] 50 Kbps
[19] 100 Kbps
[20] * 125 Kbps
[21] 250 Kbps
[22] 500 Kbps
DN-02 MAC ID
Range: Function:
63.* [0 - 63.] Selection of station address. Every station connected to the same network must have an unambiguous
address.
DN-05 Readout Transmit Error Counter
Range: Function:
0* [0 - 4294967296] View the number of CAN control transmission errors since the last power-up.
DN-06 Readout Receive Error Counter
Range: Function:
0* [0 - 4294967296] View the number of CAN control receipt errors since the last power-up.
DN-07 Readout Bus Off Counter
Range: Function:
0* [0 - 255] View the number of Bus Off events since the last power-up.
AF-650 GP Programming Guide
123
3