3.12 PB-## Profibus
Parameter group related to Field Installed Profibus DP Network Communications Option Module.
PB-00 Setpoint
Range: Function:
0* [0 - 65535] This parameter receives cyclical reference from a Master Class 2. If the control priority is set to Master
Class 2, the reference for the frequency converter is taken from this parameter, whereas the cyclical
reference will be ignored.
PB-07 Actual Value
Range: Function:
0* [0 - 65535] This parameter delivers the MAV for a Master Class 2. The parameter is valid if the control priority is set
to Master Class 2.
PB-15 PCD Write Configuration
Array [10]
Option: Function:
Select the parameters to be assigned to PCD 3 to 10 of the messages. The number of available PCDs
depends on the message type. The values in PCD 3 to 10 will then be written to the selected parameters
as data values. Alternatively, specify a standard Profibus message in par. PB-22 Telegram Selection.
PB-16 PCD Read Configuration
Array [10]
Option: Function:
Select the parameters to be assigned to PCD 3 to 10 of the messages. The number of available PCDs
depends on the message type. PCDs 3 to 10 contain the actual data values of the selected parameters.
For standard Profibus messages, see par. PB-22 Telegram Selection.
PB-18 Node Address
Range: Function:
126* [0 - 126.] Enter the station address in this parameter or alternatively in the hardware switch. In order to adjust the
station address in par. PB-18 Node Address, the hardware switch must be set to 126 or 127 (i.e. all switches
set to ‘on’). Otherwise this parameter will display the actual setting of the switch.
PB-22 Telegram Selection
Displays the Profibus message configuration.
Option: Function:
[1] Standard telegram 1
[101] PPO 1
[102] PPO 2
[103] PPO 3
[104] PPO 4
[105] PPO 5
[106] PPO 6
[107] PPO 7
[108] * PPO 8 Read only.
[200] Custom telegram 1