3.7 H-## High Perf Parameters
Parameter group related to high performance functions in the drive.
3.7.1 H-0# High Perf Operations
Parameters to restore factory setting, configure auto reset, fan operation, reverse lock and start mode (catch a spinning load).
H-03 Restore Factory Settings
Option: Function:
Use this parameter to specify normal operation, to perform tests or to initialise all parameters except
par. ID-03 Power Up's, par. ID-04 Over Temp's and par. ID-05 Over Volt's. This function is active only when
the power is cycled (power off-power on) to the frequency converter.
[0] * Normal operation Select Normal operation [0] for normal operation of the frequency converter with the motor in the selected
application.
[2] Restore Factory Settings Select Initialization [2] to reset all parameter values to default settings, except for par. ID-03 Power Up's,
par. ID-04 Over Temp's and par. ID-05 Over Volt's. The frequency converter will reset during the next power-
up.
par. H-03 Restore Factory Settings will also revert to the default setting Normal operation [0].
[3] Boot mode
H-04 Auto-Reset (Times)
Option: Function:
Select the reset function after tripping. Once reset, the frequency converter can be restarted.
[0] * Manual reset Select Manual reset [0], to perform a reset via [RESET] or via the digital inputs.
[1] Automatic reset x 1 Select Automatic reset x 1…x20 [1]-[12] to perform between one and twenty automatic resets after trip-
ping.
[2] Automatic reset x 2
[3] Automatic reset x 3
[4] Automatic reset x 4
[5] Automatic reset x 5
[6] Automatic reset x 6
[7] Automatic reset x 7
[8] Automatic reset x 8
[9] Automatic reset x 9
[10] Automatic reset x 10
[11] Automatic reset x 15
[12] Automatic reset x 20
[13] Infinite auto reset Select Infinite Automatic Reset [13] for continuous resetting after tripping.
NB!
The motor may start without warning. If the specified number of AUTOMATIC RESETs is reached within 10 minutes, the frequency converter enters Manual reset
[0] mode. After the Manual reset is performed, the setting of par. H-04 Auto-Reset (Times) reverts to the original selection. If the number of automatic resets is
not reached within 10 minutes, or when a Manual reset is performed, the internal AUTOMATIC RESET counter returns to zero.
NB!
Automatic reset will also be active for resetting safe stop function in firmware version < 4.3x.