3.3 Parameter Data Set
Parameter group related to the fundamental functions of the drive.
3.3.1 F-0# Fundamental 0
Parameters to configure frequency command, base speed settings, Torque Boost, and accel/decel time.
F-01 Frequency Setting 1
Option: Function:
Select the reference input to be used for the first reference signal. par. F-01 Frequency Setting 1, par.
C-30 Frequency Command 2 and par. C-34 Frequency Command 3 define up to three different reference
signals. The sum of these reference signals defines the actual reference.
[0] No function
[1] * Analog Input 53
[2] Analog Input 54
[7] Frequency input 29
[8] Frequency input 33
[11] Local bus reference
[20] Digital Potentio-Meter
[21] Analog input X30-11 (OPCGPIO - General Purpose I/O Option Module)
[22] Analog input X30-12 (OPCGPIO - General Purpose I/O Option Module)
F-02 Operation Method
Option: Function:
Select which reference site to activate.
[0] * Linked to Hand / Auto Use local reference when in Hand mode; or remote reference when in Auto mode.
[1] Remote Use remote reference in both Hand mode and Auto mode.
[2] Local Use local reference in both Hand mode and Auto mode.
NB!
When set to Local [2], the frequency converter will start with this setting again following a 'power down'.
F-03 Max Output Frequency 1
Range: Function:
132.0 Hz* [1.0 - 1000.0 Hz] Provides a final limit on the output frequency for improved safety in applications where you want to avoid
accidental over-speeding. This limit is final in all configurations (independent of the setting in par.
H-40 Configuration Mode).
NB!
Max. output frequency cannot exceed 10% of the inverter switching frequency (par. F-26 Motor Noise (Carrier Freq)).
par. F-03 Max Output Frequency 1 cannot be adjusted while the motor is running.
F-04 Base Frequency
Range: Function:
50. Hz* [20 - 1000 Hz] Min - Max motor frequency: 20 - 1000 Hz.