3.14 RS-## Resolver Interface
RS-50 Poles
Range: Function:
2* [2 - 2] Set the number of poles on the resolver.
The value is stated in the data sheet for resolvers.
RS-51 Input Voltage
Range: Function:
7.0 V* [2.0 - 8.0 V] Set the input voltage to the resolver. The voltage is stated as RMS value.
The value is stated in the data sheet for resolvers
RS-52 Input Frequency
Range: Function:
10.0 kHz* [2.0 - 15.0 kHz] Set the input frequency to the resolver.
The value is stated in the data sheet for resolvers.
RS-53 Transformation Ratio
Range: Function:
0.5* [0.1 - 1.1] Set the transformation ratio for the resolver.
The transformation ration is:
T
ratio
=
V
Out
V
In
The value is stated in the data sheet for resolvers.
RS-59 Resolver Interface
Activate the OPCRES resolver option when the resolver parameters are selected.
To avoid damage to resolvers par. RS-50 Poles – par. RS-53 Transformation Ratio must be adjusted before activating this parameter.
Option: Function:
[0] * Disabled
[1] Enabled