Reversing
Set-up select lsb - Set-up select msb
Stop command from serial communication
•Quick stop
DC brake
[Off] stops the connected motor. The key can be selected as Enable [1] or Disable [0] via par. K-41 [Off] Button on Keypad .
If no external stop function is selected and the [Off] key is inactive the motor can be stopped by disconnecting the voltage.
[Auto] enables the frequency converter to be controlled via the control terminals and/or serial communication. When a start signal is applied on the control
terminals and/or the bus, the frequency converter will start. The key can be selected as Enable [1] or Disable [0] via par. K-42 [Auto] Button on Keypad.
NB!
An active HAND-OFF-AUTO signal via the digital inputs has higher priority than the control keys [Hand] [Auto].
[Reset] is used for resetting the frequency converter after an alarm (trip). It can be selected as Enable [1] or Disable [0] via par. K-43 [Reset] Button on Keypad.
2.1.18 Restoring Drive to Factory Settings
The drive can be restored to factory settings in two ways:
Recommended
1. Select par. H-03 Restore Factory Settings
2. Press [OK]
3. Select [2] Restore Factory Settings
4. Press [OK]
5. Cut off the mains supply and wait until the display turns off.
6. Reconnect the mains supply - the frequency converter is now reset.
par. H-03 Restore Factory Settings restores all except:
par. SP-50 RFI Filter
par. O-30 Protocol
par. O-31 Address
par. O-32 Drive Port Baud Rate
par. O-35 Minimum Response Delay
par. O-36 Max Response Delay
par. O-37 Max Inter-Char Delay
par. ID-00 Operating Hours to par. ID-05 Over Volt's
par. ID-20 Historic Log: Event to par. ID-22 Historic Log: Time
par. ID-30 Fault Log: Error Code to par. ID-32 Alarm Log: Time
Manual Restore of Factory Settings
1. Disconnect from mains and wait until the display turns off
2. Press [Status] - [Main Menu] - [OK] at the same time while power up for Keypad
3. Release the keys after 5 s.
4. The frequency converter is now programmed according to default settings.
Manual restores all except:
par. ID-00 Operating Hours
par. ID-03 Power Up's
par. ID-04 Over Temp's
par. ID-05 Over Volt's
NB!
When you carry out manual restore, you also reset serial communication, RFI filter settings (par. SP-50 RFI Filter) and fault log settings.
AF-650 GP Programming Guide
24