3.15 Parameter Data Check
3.15.1 Last 10 Changes
Displays a list of the 10 last changes made to the parameters in the present parameter setup. This allows for any corrections of the last 10 changes.
3.15.2 Since Factory Settings
Displays a list of all the parameter changes since the factory settings of the drive or since the last factory restore of parameters.
3.16 ID-## Drive Information
Parameter group related to drive information such as operating data, hardware configuration and software version.
3.16.1 ID-0# Operating Data
Parameters to view operating hours. kWh counters, power ups, etc.
ID-00 Operating Hours
Range: Function:
0 h* [0 - 2147483647 h] View how many hours the frequency converter has run. The value is saved when the frequency converter
is turned off.
ID-01 Running Hours
Range: Function:
0 h* [0 - 2147483647 h] View how many hours the motor has run. Reset the counter in par. ID-07 Reset Running Hours Counter.
The value is saved when the frequency converter is turned off.
ID-02 kWh Counter
Range: Function:
0 kWh* [0 - 2147483647 kWh] Registering the power consumption of the motor as a mean value over one hour. Reset the counter in
par. ID-06 Reset kWh Counter.
ID-03 Power Up's
Range: Function:
0* [0 - 2147483647] View the number of times the frequency converter has been powered up.
ID-04 Over Temp's
Range: Function:
0* [0 - 65535] View the number of frequency converter temperature faults which have occurred.
ID-05 Over Volt's
Range: Function:
0* [0 - 65535] View the number of frequency converter overvoltages which have occurred.
ID-06 Reset kWh Counter
Option: Function:
[0] * Do not reset Select Do not reset [0] if no reset of the kWh counter is desired.
[1] Reset counter Select Reset [1] and press [OK] to reset the kWh counter to zero (see par. ID-02 kWh Counter).
AF-650 GP Programming Guide
135