Par. No. # Parameter description Default value 4-set-up Change during opera-
tion
Conver-
sion index
Type
F-0#
F-01 Frequency Setting 1 null All set-ups TRUE - Uint8
F-02 Operation Method [0] Linked to Hand / Auto All set-ups TRUE - Uint8
F-03 Max Output Frequency 1 132.0 Hz All set-ups FALSE -1 Uint16
F-04 Base Frequency ExpressionLimit All set-ups FALSE 0 Uint16
F-05 Motor Rated Voltage ExpressionLimit All set-ups FALSE 0 Uint16
F-07 Accel Time 1 ExpressionLimit All set-ups TRUE -2 Uint32
F-08 Decel Time 1 ExpressionLimit All set-ups TRUE -2 Uint32
F-09 Torque Boost 100 % All set-ups TRUE 0 Int16
F-1#
F-10 Electronic Overload [0] No protection All set-ups TRUE - Uint8
F-11 Motor External Fan [0] No All set-ups TRUE - Uint16
F-12 Motor Thermistor Input [0] None All set-ups TRUE - Uint8
F-15 Motor Speed High Limit [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
F-16 Motor Speed Low Limit [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
F-17 Motor Speed High Limit [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
F-18 Motor Speed Low Limit [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
F-2#
F-22 Start Speed [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
F-23 Start Speed [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
F-24 Holding Time 0.0 s All set-ups TRUE -1 Uint8
F-25 Start Function [2] Coast/delay time All set-ups TRUE - Uint8
F-26 Motor Noise (Carrier Freq) null All set-ups TRUE - Uint8
F-27 Motor Tone Random [0] Off All set-ups TRUE - Uint8
F-29 Start Current 0.00 A All set-ups TRUE -2 Uint32
F-3#
F-37 Adv. Switching Pattern [1] SFAVM All set-ups TRUE - Uint8
F-38 Overmodulation [1] On All set-ups FALSE - Uint8
F-4#
F-40 Torque Limiter (Driving) ExpressionLimit All set-ups TRUE -1 Uint16
F-41 Torque Limiter (Braking) 100.0 % All set-ups TRUE -1 Uint16
F-43 Current Limit ExpressionLimit All set-ups TRUE -1 Uint32
F-5#
F-50 Reference Range null All set-ups TRUE - Uint8
F-51 Reference/Feedback Unit null All set-ups TRUE - Uint8
F-52 Minimum Reference 0 ReferenceFeedbackUnit All set-ups TRUE -3 Int32
F-53 Maximum Reference ExpressionLimit All set-ups TRUE -3 Int32
F-54 Reference Function [0] Sum All set-ups TRUE - Uint8
F-6#
F-62 Catch up/slow Down Value 0.00 % All set-ups TRUE -2 Int16
F-64 Preset Relative Reference 0.00 % All set-ups TRUE -2 Int32
F-68 Relative Scaling Reference Resource [0] No function All set-ups TRUE - Uint8
F-9#
F-90 Step Size 0.10 % All set-ups TRUE -2 Uint16
F-91 Accel/Decel Time 1.00 s All set-ups TRUE -2 Uint32
F-92 Power Restore [0] Off All set-ups TRUE - Uint8
F-93 Maximum Limit 100 % All set-ups TRUE 0 Int16
F-94 Minimum Limit -100 % All set-ups TRUE 0 Int16
F-95 Accel/Decel Ramp Delay ExpressionLimit All set-ups TRUE -3 TimD