Par. No. # Parameter description Default value 4-set-up Change during opera-
tion
Conver-
sion index
Type
AN-0#
AN-00 Live Zero Timeout Time 10 s All set-ups TRUE 0 Uint8
AN-01 Live Zero Timeout Function [0] Off All set-ups TRUE - Uint8
AN-1#
AN-10 Terminal 53 Low Voltage 0.07 V All set-ups TRUE -2 Int16
AN-11 Terminal 53 High Voltage 10.00 V All set-ups TRUE -2 Int16
AN-12 Terminal 53 Low Current 4.00 mA All set-ups TRUE -5 Int16
AN-13 Terminal 53 High Current 20.00 mA All set-ups TRUE -5 Int16
AN-14 Terminal 53 Low Ref./Feedb. Value 0.000 All set-ups TRUE -3 Int32
AN-15 Terminal 53 High Ref./Feedb. Value ExpressionLimit All set-ups TRUE -3 Int32
AN-16 Terminal 53 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint16
AN-17 Terminal 53 Live Zero [1] Enabled All set-ups TRUE - Uint8
AN-2#
AN-20 Terminal 54 Low Voltage 0.07 V All set-ups TRUE -2 Int16
AN-21 Terminal 54 High Voltage 10.00 V All set-ups TRUE -2 Int16
AN-22 Terminal 54 Low Current 4.00 mA All set-ups TRUE -5 Int16
AN-23 Terminal 54 High Current 20.00 mA All set-ups TRUE -5 Int16
AN-24 Terminal 54 Low Ref./Feedb. Value 0.000 All set-ups TRUE -3 Int32
AN-25 Terminal 54 High Ref./Feedb. Value 100.000 All set-ups TRUE -3 Int32
AN-26 Terminal 54 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint16
AN-27 Terminal 54 Live Zero [1] Enabled All set-ups TRUE - Uint8
AN-3#
AN-30 Terminal X30/11 Low Voltage (OPCGPIO) 0.07 V All set-ups TRUE -2 Int16
AN-31 Terminal X30/11 High Voltage (OPCGPIO) 10.00 V All set-ups TRUE -2 Int16
AN-34 Term. X30/11 Low Ref./Feedb. Value (OPCGPIO) 0.000 All set-ups TRUE -3 Int32
AN-35 Term. X30/11 High Ref./Feedb. Value (OPCGPIO) 100.000 All set-ups TRUE -3 Int32
AN-36 Term. X30/11 Filter Time Constant (OPCGPIO) 0.001 s All set-ups TRUE -3 Uint16
AN-37 Term. X30/11 Live Zero(OPCGPIO) [1] Enabled All set-ups TRUE - Uint8
AN-4#
AN-40 Terminal X30/12 Low Voltage (OPCGPIO) 0.07 V All set-ups TRUE -2 Int16
AN-41 Terminal X30/12 High Voltage (OPCGPIO) 10.00 V All set-ups TRUE -2 Int16
AN-44 Term. X30/12 Low Ref./Feedb. Value (OPCGPIO) 0.000 All set-ups TRUE -3 Int32
AN-45 Term. X30/12 High Ref./Feedb. Value (OPCGPIO) 100.000 All set-ups TRUE -3 Int32
AN-46 Term. X30/12 Filter Time Constant (OPCGPIO) 0.001 s All set-ups TRUE -3 Uint16
AN-47 Term. X30/12 Live Zero (OPCGPIO) [1] Enabled All set-ups TRUE - Uint8
AN-5#
AN-50 Terminal 42 Output null All set-ups TRUE - Uint8
AN-51 Terminal 42 Output Min Scale 0.00 % All set-ups TRUE -2 Int16
AN-52 Terminal 42 Output Max Scale 100.00 % All set-ups TRUE -2 Int16
AN-53 Terminal 42 Output Bus Control 0.00 % All set-ups TRUE -2 N2
AN-54 Terminal 42 Output Timeout Preset 0.00 % 1 set-up TRUE -2 Uint16
AN-6#
AN-60 Terminal X30/8 Output (OPCGPIO) [0] No operation All set-ups TRUE - Uint8
AN-61 Terminal X30/8 Min. Scale (OPCGPIO) 0.00 % All set-ups TRUE -2 Int16
AN-62 Terminal X30/8 Max. Scale (OPCGPIO) 100.00 % All set-ups TRUE -2 Int16
AN-63 Terminal X30/8 Output Bus Control (OPCGPIO) 0.00 % All set-ups TRUE -2 N2
AN-64 Terminal X30/8 Output Timeout Preset (OPCGPIO) 0.00 % 1 set-up TRUE -2 Uint16