ID-21 Historic Log: Value
Array [50]
Range: Function:
0* [0 - 2147483647] View the value of the logged event. Interpret the event values according to this table:
Digtal input Decimal value. See par. DR-60 Digital Input for description after
converting to binary value.
Digital output (not monitored in this
SW release)
Decimal value. See par. DR-66 Digital Output [bin] for descrip-
tion after converting to binary value.
Warning word Decimal value. See par. DR-92 Warning Word for description.
Alarm word Decimal value. See par. DR-90 Alarm Word for description.
Status word Decimal value. See par. DR-03 Status Word for description after
converting to binary value.
Control word Decimal value. See par. DR-00 Control Word for description.
Extended status word Decimal value. See par. DR-94 Ext. Status Word for description.
ID-22 Historic Log: Time
Array [50]
Range: Function:
0 ms* [0 - 2147483647 ms] View the time at which the logged event occurred. Time is measured in ms since frequency converter
start. The max. value corresponds to approx. 24 days which means that the count will restart at zero after
this time period.
3.16.4 ID-3# Alarm Log
View up to 10 alarm logs. The data is stored in array parameters, where [0] is the most recent and [9] is the oldest data. Error codes, values, and time stamp can
be viewed for all logged data.
ID-30 Fault Log: Error Code
Array [10]
Range: Function:
0* [0 - 255] View the error code and look up its meaning in the Troubleshooting chapter of the AF-650 GP Design
Guide.
ID-31 Alarm Log: Value
Array [10]
Range: Function:
0* [-32767 - 32767] View an extra description of the error. This parameter is mostly used in combination with alarm 38 ‘internal
fault’.
ID-32 Alarm Log: Time
Array [10]
Range: Function:
0 s* [0 - 2147483647 s] View the time when the logged event occurred. Time is measured in seconds from frequency converter
start-up.
3.16.5 ID-4# Drive Identification
Parameters to view the information about the hardware and software configuration of the drive.
ID-40 Drive Type
Range: Function:
0* [] View the Drive type.