DR-63 Terminal 54 Switch Setting
Option: Function:
View the setting of input terminal 54. Current = 0; Voltage = 1.
[0] * Current
[1] Voltage
[2] Pt 1000 [°C]
[3] Pt 1000 [°F]
[4] Ni 1000 [°C]
[5] Ni 1000 [°F]
DR-64 Analog Input 54
Range: Function:
0.000* [-20.000 - 20.000] View the actual value at input 54.
DR-65 Analog Output 42 [mA]
Range: Function:
0.000* [0.000 - 30.000] View the actual value at output 42 in mA. The value shown reflects the selection in par. AN-50 Terminal
42 Output.
DR-66 Digital Output [bin]
Range: Function:
0* [0 - 15] View the binary value of all digital outputs.
DR-67 Freq. Input #29 [Hz]
Range: Function:
0* [0 - 130000] View the actual frequency rate on terminal 29.
DR-68 Freq. Input #33 [Hz]
Range: Function:
0* [0 - 130000] View the actual value of the frequency applied at terminal 33 as an impulse input.
DR-69 Pulse Output #27 [Hz]
Range: Function:
0* [0 - 40000] View the actual value of pulses applied to terminal 27 in digital output mode.
DR-70 Pulse Output #29 [Hz]
Range: Function:
0* [0 - 40000] View the actual value of pulses at terminal 29 in digital output mode.
DR-71 Relay Output [bin]
Range: Function:
0* [0 - 511] View the settings of all relays.
AF-650 GP Programming Guide
146
3