EC-34 HIPERFACE Baudrate
Select the baud rate of the attached encoder.
This parameter cannot be adjusted while the motor is running. The parameter is only accessible when par. EC-20 Protocol Selection is set to HIPERFACE [1].
Option: Function:
[0] 600
[1] 1200
[2] 2400
[3] 4800
[4] * 9600
[5] 19200
[6] 38400
3.13.3 EC-6# Monitoring and App.
EC-60 Feedback Direction
Change the detected encoder rotation direction without changing the wiring to the encoder.
This parameter cannot be adjusted while the motor is running.
Option: Function:
[0] * Clockwise
[1] Counter clockwise
EC-61 Feedback Signal Monitoring
Select which reaction the frequency converter should take in case a faulty encoder signal is detected.
The encoder function in par. EC-61 Feedback Signal Monitoring is an electrical check of the hardware circuit in the encoder system.
Option: Function:
[0] Disabled
[1] * Warning
[2] Trip
[3] Jog
[4] Freeze Output
[5] Max Speed
[6] Switch to Open Loop
[7] Select Setup 1
[8] Select Setup 2
[9] Select Setup 3
[10] Select Setup 4
[11] stop & trip
AF-650 GP Programming Guide
133