in par. H-21 Motor Feedback Speed Error during its time frame set in par. H-22 Motor Feedback Loss
Timeout.
[0] Disabled
[1] Warning
[2] * Trip
[3] Jog
[4] Freeze Output
[5] Max Speed
[6] Switch to Open Loop
[7] Select Setup 1
[8] Select Setup 2
[9] Select Setup 3
[10] Select Setup 4
[11] stop & trip
H-21 Motor Feedback Speed Error
Range: Function:
300 RPM* [1 - 600 RPM] Select the max allowed tracking error in speed from the calculated and the actual mechanical shaft output
speed.
H-22 Motor Feedback Loss Timeout
Range: Function:
0.05 s* [0.00 - 60.00 s] Set the timeout value allowing the speed error set in par. H-21 Motor Feedback Speed Error to be exceeded.
3.7.3 H-4# Advanced Settings
Parameters to configure advanced controls for Open/Closed Loop, control principles: V/Hz, Adv. Vector, Sensorless Vector, and Closed Loop Vector, Constant or
Variable Torque, and Overload Mode.
H-40 Configuration Mode
Option: Function:
Select the application control principle to be used when a Remote Reference (i.e. via analog input or
Network) is active. A Remote Reference can only be active when par. F-02 Operation Method is set to [0]
or [1].