O-55 Set-up Select
Option: Function:
Select control of the frequency converter set-up selection via the terminals (digital input) and/or via the
network.
[0] Digit Input Activates the set-up selection via a digital input.
[1] Bus Activates the set-up selection via the serial communication port or network option module.
[2] Logic AND Activates the set-up selection via the network/serial communication port, AND additionally via one of the
digital inputs.
[3] * Logic OR Activate the set-up selection via the network/serial communication port OR via one of the digital inputs.
NB!
This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.
O-56 Preset Reference Select
Option: Function:
Select control of the frequency converter Preset Reference selection via the terminals (digital input) and/
or via the network.
[0] Digit Input Activates Preset Reference selection via a digital input.
[1] Bus Activates Preset Reference selection via the serial communication port or network option module.
[2] Logic AND Activates Preset Reference selection via the network/serial communication port, AND additionally via one
of the digital inputs.
[3] * Logic OR Activates the Preset Reference selection via the network/serial communication port OR via one of the
digital inputs.
NB!
This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.
3.10.6 O-8# Drive Port Diagnostics
O-80 Bus Message Count
Range: Function:
0* [0 - 4294967296] This parameter shows the number of valid messages detected on the network.
O-81 Bus Error Count
Range: Function:
0* [0 - 4294967296] This parameter shows the number of messages with faults (e.g. CRC fault), detected on the network.
O-82 Slave Messages Rcvd
Range: Function:
0* [0 - 4294967296] This parameter shows the number of valid messages addressed to the slave, sent by the frequency
converter.
O-83 Slave Error Count
Range: Function:
0* [0 - 4294967296] This parameter shows the number of error messages, which could not be executed by the frequency
converter.
AF-650 GP Programming Guide
121
3