2.1.8 Initial Commissioning
The easiest way of carrying out the initial commissioning is by using the Quick Menu button and follow the quick set-up procedure using Keypad (read table from
left to right). The example applies to open loop applications:
Press
Quick Start
par. K-01 Language Set language
par. K-02 Motor Speed Unit Set motor speed in Hz or RPM
par. P-02 Motor Power [HP] or par. P-07 Motor
Power [kW]
Set Motor nameplate power
par. F-05 Motor Rated Voltage Set Nameplate voltage
par. F-04 Base Frequency
Set Nameplate frequency
par. P-03 Motor Current Set Nameplate current
par. P-06 Base Speed
Set Nameplate speed in RPM
par. F-01 Frequency Setting 1 Set reference source
par. F-02 Operation Method
Select which reference site to activate
par. F-07 Accel Time 1
Set the accel time with reference to synchronous motor speed, n
s
par. F-08 Decel Time 1
Set the decel time time with reference to synchronous motor speed,
n
s
par. F-10 Electronic Overload Set motor thermal protection
par. F-15 Motor Speed High Limit [Hz] or par.
F-17 Motor Speed High Limit [RPM]
Set motor speed high limit in Hz or RPM
par. F-16 Motor Speed Low Limit [Hz] or par.
F-18 Motor Speed Low Limit [RPM]
Set motor speed low limit in Hz or RPM
par. H-08 Reverse Lock
Set allowed rotation direction
par. P-04 Auto Tune
Set desired auto tune function. Enable complete auto tune is rec-
ommended