H-70 Warning Current Low
Range: Function:
0.00 A* [0.00 - par. H-51 A] Enter the I
LOW
value. When the motor current falls below this limit, the display reads Current Low. The
signal outputs can be programmed to produce a status signal on terminal 27 or 29 and on relay output
01 or 02. Refer to the drawing in this section.
H-71 Warning Current High
Range: Function:
par. AP-37
A*
[par. H-50 - par. AP-37 A] Enter the I
HIGH
value. When the motor current exceeds this limit, the display reads Current High. The signal
outputs can be programmed to produce a status signal on terminal 27 or 29 and on relay output 01 or
02. Refer to the drawing in this section.
H-72 Warning Speed Low
Range: Function:
0 RPM* [0 - par. H-53 RPM] Enter the n
LOW
value. When the motor speed exceeds this limit, the display reads Speed Low. The signal
outputs can be programmed to produce a status signal on terminal 27 or 29 and on relay output 01 or
02.
H-73 Warning Speed High
Range: Function:
par. H-13
RPM*
[par. H-52 - par. H-13 RPM] Enter the n
HIGH
value. When the motor speed exceeds this limit, the display reads Speed High. The signal
outputs can be programmed to produce a status signal on terminal 27 or 29 and on relay output 01 or
02. Programme the upper signal limit of the motor speed, n
HIGH
, within the normal working range of the
frequency converter. Refer to the drawing in this section.
H-74 Warning Reference Low
Range: Function:
-999999.99
9*
[-999999.999 - par. H-75] Enter the lower reference limit. When the actual reference falls below this limit, the display indicates Ref
Low. The signal outputs can be programmed to produce a status signal on terminal 27 or 29 and on relay
output 01 or 02.
H-75 Warning Reference High
Range: Function:
999999.999
*
[par. H-74 - 999999.999] Enter the upper reference limit. When the actual reference exceeds this limit, the display reads Ref High.
The signal outputs can be programmed to produce a status signal on terminal 27 or 29 and on relay
output 01 or 02.
H-76 Warning Feedback Low
Range: Function:
-999999.99
9*
[-999999.999 - par. H-77] Enter the lower feedback limit. When the feedback falls below this limit, the display reads Feedb Low. The
signal outputs can be programmed to produce a status signal on terminal 27 or 29 and on relay output
01 or 02.
H-77 Warning Feedback High
Range: Function:
999999.999
*
[par. H-76 - 999999.999] Enter the upper feedback limit. When the feedback exceeds this limit, the display reads Feedb High. The
signal outputs can be programmed to produce a status signal on terminal 27 or 29 and on relay output
01 or 02.
AF-650 GP Programming Guide
96