DET-653C EntelliGuard
®
G Circuit Breaker Application Guide
24-May-12 Section 5. Catalog Numbering Guide
©2012 General Electric All Rights Reserved
67
Digit 18 Zone Selective Interlocking (ZSI)
Zone Selective Interlocking
Code
ZSI, Short time and GF; user selectable
Z
Z + IOC or HIOC ZSI; user selectable
T
Blank/none
X
ZSI selections require Secondary Disconnect Block B and 24Vdc control
power. Control power recommended for instantaneous ZSI.
Digit 19 Advanced Features and Communications
Advanced Features and Communications
Code
Reduced Energy Let-Through (RELT)
1
Modbus Protocol + RELT
2
Profibus Protocol + RELT
3
Monitoring + RELT, NO Communication
4
Monitoring + Relay Package + RELT
5
Monitoring + Data Acquisition, Modbus
Protocol + RELT
6
Monitoring + Data Acquisition, Profibus
Protocol + RELT
7
Monitoring + Data Acquisition + Relay Package,
Modbus + RELT
8
Monitoring + Data Acquisition + Relay Package,
Profibus + RELT
9
None
X
.All Advanced Feature selections require Secondary Disconnect Block B
and 24Vdc control Power.
Option "X" is the only valid option when a Switch is selected in Digit 2.
RELT = Reduced Energy Let Through, requires dedicated input and output
on the CB Monitoring = Advanced Metering.
Data Acquisition = Waveform Capture and Harmonic Analysis .
In order to output the Coil Signaling status HiFi via trip unit (Digit 12,
Options B, D, F, H, K, M, P, R, T, and V) a communications package must
be selected in Advanced Features (Digit 19; options 2, 3, ,7, 8, 9). This
option requires Secondary Disconnect Block B.
In order to output the RTC contact output via Trip Unit (Digit 13; Options
3, F, J, M) a communications package must be selected in Advanced
Features (Code 19/Step 16); this requires Secondary Disconnect Block B.
Digit 20 Rating Plug
Rating Plug
Catalog Number
Code
150
GTP0150U0104
B
200 GTP0200U0204 C
225 GTP0225U0306 D
250 GTP0250U0407 E
300 GTP0300U0408 F
350 GTP0350U0408 G
400 GTP0400U0410 H
450 GTP0450U0612 I
500 GTP0500U0613 J
600 GTP0600U0616 K
700 GTP0700U0816 M
750 GTP0750U0820 N
800 GTP0800U0820 O
900 GTP0900U1020 P
1000 GTP1000U1025 Q
1100
GTP1100U1225
R
1200 GTP1200U1232 S
1500 GTP1500U1640 U
1600 GTP1600U1640 V
1900
GTP1900U2050
W
2000 GTP2000U2050 Y
2200 GTP2200U2550 Z
2400 GTP2400U2564 1
2500
GTP2500U2564
2
3000 GTP3000U3064 3
3200 GTP3200U3264 4
3600 GTP3600U4064 5
4000 GTP4000U4064 6
5000 GTP5000U5064 7
6000
GTP6000U6064
8
Rating plug not required/non auto switch
X
See Section 3 for further details on rating plugs and sensors.
Option "X" is the only valid option when a switch is selected in Digit 2.