5–80 489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
FIGURE 5–18: Voltage Dependent Overload Curve (Custom)
Z Enter the per unit current value for the acceleration overload curve
intersect with the custom curve for 80% voltage.
Z Enter the per unit current and safe stall protection time for 80% voltage
(see the acceleration curves below).
Z Enter the per unit current value for the acceleration overload curve
intersect with the custom curve for 100% voltage.
Z Enter the per unit current and safe stall protection time for 100% voltage
(see the acceleration curves below).