S1 745 Setup745
Transformer Management Relay
Setpoints
http://www.GEindustrial.com/multilin
5–26
GE Multilin
changed via the communication ports. If the four wire RS422 hardware
configuration is required, select RS422.
FRONT BAUD RATE / FRONT PARITY: Select the baud rate / parity for the
front panel port. These setpoints cannot be changed via communication ports.
c) DNP Communications
PATH: SETPOINTS ! S1 745 SETUP !" COMMUNICATIONS !" DNP
DNP PORT: Selects the communication port for DNP communications.
DNP POINT MAPPING: When enabled, the 120 User Map Values are included
in the DNP Object 30 point list. For additional information, refer to GE
publication GEK-106636: 745 Communications Guide.
TRANSMISSION DELAY: Select the minimum time from when a DNP request
is received and a response issued. A value of zero causes the response to be
issued as quickly as possible.
DATA LINK CONFIRM MODE: Select the data link confirmation mode for
responses sent by the 745. When Sometimes is selected, data link confirmation
is only requested when the response contains more than one frame.
DATA LINK CONFIRM TIMEOUT: Selects a desired timeout. If no
confirmation response is received within this time, the 745 will re-send the
frame if retries are still available.
DATA LINK CONFIRM RETRIES: Select the maximum number of retries that
will be issued for a given data link frame.
SELECT/OPERATE ARM TIMEOUT: Select the duration of the select / operate
arm timer.
WRITE TIME INTERVAL: Select the time that must elapse before the 745 will
set the ‘need time’ internal indication (IIN). After the time is written by a DNP
master, the IIN will be set again after this time elapses. A value of zero disables
this feature.
COLD RESTART INHIBIT: When disabled, a cold restart request from a DNP
master will cause the 745 to be reset. Enabling this setpoint will cause the cold
restart request to initialize only the DNP sub-module.
When “Disabled” is selected, a cold restart request will cause loss of
protection until the 745 reset completes.
! DNP [!] DNP PORT:
None
Range: None, COM1, COM2, Front
MESSAGE
DNP POINT MAPPING:
Enabled
Range: Enabled, Disabled
MESSAGE
TRANSMISSION DELAY:
0 ms
Range: 0 to 65000 ms in steps of 1
MESSAGE
DATA LINK CONFIRM
MODE: Never
Range: Never, Always, Sometimes
MESSAGE
DATA LINK CONFIRM
TIMEOUT: 1000 ms
Range: 1 to 65000 ms in steps of 1
MESSAGE
DATA LINK CONFIRM
RETRIES: 3
Range: 0 to 100 in steps of 1
MESSAGE
SELECT/OPERATE ARM
TIMEOUT: 10000 ms
Range: 1 to 65000 ms in steps of 1
MESSAGE
WRITE TIME INTERVAL:
0 ms
Range: 0 to 65000 ms in steps of 1
MESSAGE
COLD RESTART
INHIBIT: Disabled
Range: Enabled, Disabled
WARNING