A2 Metering
745
Transformer Management Relay
Actual Values
http://www.GEindustrial.com/multilin
6–7
GE Multilin
f) Differential Current
PATH: ACTUAL VALUES !" A2 METERING ! CURRENT !" DIFFERENTIAL
The differential current magnitudes and angles for Phases A, B, and C are shown.
The differential current phase angles are referenced to Winding 1 Phase A current.
g) Restraint Current
PATH: ACTUAL VALUES !" A2 METERING ! CURRENT !" RESTRAINT
The restraint current magnitudes for phases A, B, and C are shown here.
h) Ground Differential Current
PATH: ACTUAL VALUES !" A2 METERING ! CURRENT !" GROUND DIFFERENTIAL
The ground differential current magnitudes for Windings 1 through 3 are shown.
! DIFFERENTIAL [!] PHASE A DIFFERENTIAL
CURRENT: 0.00 x CT
MESSAGE
PHASE A DIFFERENTIAL
ANGLE: 0° Lag
MESSAGE
PHASE B DIFFERENTIAL
CURRENT: 0.00 x CT
MESSAGE
PHASE B DIFFERENTIAL
ANGLE: 0° Lag
MESSAGE
PHASE C DIFFERENTIAL
CURRENT: 0.00 x CT
MESSAGE
PHASE C DIFFERENTIAL
ANGLE: 0° Lag
! RESTRAINT [!] PHASE A RESTRAINT
CURRENT: 0.00 x CT
MESSAGE
PHASE B RESTRAINT
CURRENT: 0.00 x CT
MESSAGE
PHASE C RESTRAINT
CURRENT: 0.00 x CT
! GROUND [!]
DIFFERENTIAL
W1 GND DIFFERENTIAL
CURRENT: 0.00 x CT
MESSAGE
W2 GND DIFFERENTIAL
CURRENT: 0.00 x CT
MESSAGE
W3 GND DIFFERENTIAL
CURRENT: 0.00 x CT