Working with Setpoints and Setpoint Files
745
Transformer Management Relay
Interfaces
http://www.GEindustrial.com/multilin
4–19
GE Multilin
2. Select the Actual > Product Info menu item and record the Software Revision
identifier of the relay firmware as shown below.
3. Load the setpoint file to be upgraded into the enerVista 745 Setup environment
as described in Adding Setpoints Files to the Environment on page 4–17.
4. In the File pane, select the saved setpoint file.
5. From the main window menu bar, select the File > Properties menu item and
note the version code of the setpoint file. If this version (e.g. 4.0X shown
below) is different than the Software Revision code noted in step 2, select a
New File Version that matches the Software Revision code from the pull-down
menu.
For example, if the software revision is 2.80 and the current setpoint file
revision is 4.00, change the setpoint file revision to “4.0X”, as shown below.
6. When complete, click Convert to convert the setpoint file to the desired revision.
A dialog box will request confirmation. See Loading Setpoints from a File on
page 4–20 for instructions on loading this setpoint file into the 745.
f) Printing Setpoints and Actual Values
The enerVista 745 Setup software allows the user to print partial or complete lists of
setpoints and actual values. Use the following procedure to print a list of setpoints:
1. Select a previously saved setpoints file in the File pane or establish
communications with a 745 device.
2. From the main window, select the File > Print Settings menu item.
3. The Print/Export Options dialog box will appear. Select Settings in the upper
section and select either Include All Features (for a complete list) or Include
Select the desired setpoint version
from this menu. The 4.0x indicates
versions 4.00, 4.01, 4.02, etc.
Enter any special comments
about the setpoint file here.