42 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE
UPGRADING RELAY FIRMWARE CHAPTER 2: INSTALLATION
8. The EnerVista MM300/MM200 Setup software will notify the user when the 
MM300 MM300 has finished loading the file. Carefully read any displayed messages 
and click OK to return the main screen. Cycling power to the relay is recommended 
after a firmware upgrade.
After successfully updating the MM300 firmware, the relay will not be operational and will 
require setpoint programming. To communicate with the relay, the communication 
settings may have to be manually reprogrammed.
When communications are established, the saved setpoints must be reloaded back into 
the relay. See Loading Setpoints from a File for details.
Modbus addresses assigned to firmware modules, features, settings, and corresponding 
data items (i.e. default values, min/max values, data type, and item size) may change 
slightly from version to version of the firmware. Addresses are rearranged when new 
features are added or existing features are enhanced or modified.