122 AFE200 • Instruction Manual
15 - ALARM CONFIG
In the ALARM CONFIG menu the type of effect any alarm signals have on the AFE product is determi-
ned:
- The alarm status is saved
- How must the AFE product react to the alarm signal?
- Auto restart
- Alarm reset
For some alarms, behaviour can be congured separately for each signal, while for the others the
Disable AFE product is executed. Individual signals can also be sent to a programmable digital output.
Activity Ignore The alarm is not included in the list of alarms, it is not included in the
alarm log, it is not signalled on the digital outputs, no AFE product com-
mands are modied.
Warning The alarm is included in the list of alarms, it is included in the alarm log, it
is signalled on the digital outputs, the First alarm information is updated,
the Alarm enabled information is updated, no AFE product commands are
modied.
Disable drive The alarm is inserted in the alarm list, it is inserted in the alarm log, it is
signalled on the digital outputs, the First alarm data is updated, the Alarm
active data is updated, the AFE product is disabled.
n alarms with Activity = Ignore or Warning can be enabled at the same time.
If an alarm with Activity = Stop or Fast Stop is enabled and another alarm with an Activity other than
Ignore or Warning is enabled, the AFE product stops and is disabled
Not all alarms allow the controlled stopping of the AFE product. The following table shows the possibi-
lity of setting the Activities for the individual alarm signals.
Alarm PAR Ignore Warning Disable drive
ExtFlt activity 4504
ExtFlt restart 4506 - -
UndervoltAC activity 4534
UndervoltAC restart 4536 - -
Overvolt AC activity 4554
Overvolt AC restart 4556 - -
Drive ovld activity 4570
HTsens restart 4582 - -
InAir activity 4600
InAir restart 4602 - -
Desat restart 4610 - -
IOverC restart 4620 - -
OverV restart 4630 - -
UnderV restart 4640 - -
Optionbus activity 4670