AFE200 • Instruction Manual 123
Menu PAR Description UM Type FB BIT Def Min Max Acc
15.1 4500 Fault reset src LINK 16BIT 1120 0 16384 RW
DIGSEL2
Selection of the origin (source) of the signal to be used for the command to reset the
AFE product after an alarm. The terminal that can be used for this function can be
selected from among those listed in the “L_DIGSEL2” selection list.
Menu PAR Description UM Type FB BIT Def Min Max Acc
15.2 4502 ExtFlt src LINK 16BIT 6000 0 16384 RW
DIGSEL2
Selection of the origin (source) of the signal to be used as the input for the AFE prod-
uct External Fault [20] alarm. The terminal that can be used for this function can be
selected from among those listed in the “L_DIGSEL2” selection list.
Menu PAR Description UM Type FB BIT Def Min Max Acc
15.3 4498 Precharge fbk src LINK 16BIT 1112 0 16384 RW
L�DIGSEL1
Setting of the origin for the signal to conrm the pre-load contactor. If no conrmation
is received after a 100ms hold-off time the Prc fbk loss [23] alarm is generated (Pre-
load not conrmed).
If this parameter is set to Precharge Command (PAR 1122) the command and conr-
mation always correspond and the alarm signal us never activated.
Menu PAR Description UM Type FB BIT Def Min Max Acc
15.4 4504 ExtFlt activity ENUM Disable 0 2 RW
Setting of the behaviour of the AFE product in the event of an external fault alarm
External Fault [20]. This alarm indicates the intervention of a AFE product external
protection.
0 Ignore
1 Warning
2 Disable
Menu PAR Description UM Type FB BIT Def Min Max Acc
15.5 4506 ExtFlt restart ENUM Disabilita 0 1 RW
Enabling of automatic restart after the external fault alarm External Fault [20]
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc
15.6 4508 ExtFlt restart time ms UINT16 1000 120 30000 RW
Setting of the time within which the External Fault [20] alarm must be reset in order to
perform automatic restart.
Menu PAR Description UM Type FB BIT Def Min Max Acc
15.7 4510 ExtFlt holdoff ms UINT16 0 0 10000 RW
Setting of the delay between the signalling of the External Fault [20] alarm and ena-