This alarm indicates that the AFE product overload threshold has been reached.
0 Ignore
1 Warning
2 Disable
Menu PAR Description UM Type FB BIT Def Min Max Acc
15.15 4582 HTsens restart ENUM Disable 0 1 ERW
Enabling of automatic restart after the AFE product heatsink overtemperature alarm
HeatsinkS OTUT [12].
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc
15.16 4584 HTsens restart time ms UINT16 20000 120 60000 ERW
Setting of the time within which the HeatsinkS OTUT [12] alarm must be reset in
order to perform automatic restart.
Menu PAR Description UM Type FB BIT Def Min Max Acc
15.17 4600 InAir activity ENUM Disable 0 2 ERW
Setting of the behaviour of the AFE product in case of an intake air overtemperature
alarm InAir [13]. This alarm indicates that the temperature of the intake cooling air is
too high.
0 Ignore
1 Warning
2 Disable
Menu PAR Description UM Type FB BIT Def Min Max Acc
15.18 4602 InAir restart ENUM Disable 0 1 ERW
Enabling of automatic restart after the Intakeair OT [13] overtemperature alarm.
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc
15.19 4604 InAir restart time ms UINT16 1000 120 30000 ERW
Setting of the time within which the Intakeair OT [13] alarm must be reset in order to
perform automatic restart.
Menu PAR Description UM Type FB BIT Def Min Max Acc
15.20 4606 Air holdoff ms UINT16 10000 0 30000 ERW
Setting of the delay between the signalling of the Intakeair OT [13] overtemperature
alarm and enabling of the alarm. If an alarm condition occurs, the AFE product will
wait for the set time before enabling the alarm. If the alarm is removed within the set
time, the AFE product will not indicate any alarm condition.
Menu PAR Description UM Type FB BIT Def Min Max Acc
15.21 4610 Desat restart ENUM Disable 0 1 ERW