AFE200 • Instruction Manual 127
Menu PAR Description UM Type FB BIT Def Min Max Acc
15.29 4650 UVRep attempts UINT16 5 0 1000 ERW
Setting of the maximum number of attempts at automatic restart after the Undervolt-
age [2] alarm before a Mult Undervoltage [6] alarm is generated. If this parameter
is set to 1000 an innite number of attempts are available.
Menu PAR Description UM Type FB BIT Def Min Max Acc
15.30 4652 UVRep delay s UINT16 240 0 300 ERW
Setting of the time within which, if no automatic restarts are executed after the Und-
ervoltage [2] alarm, the attempts counter is reset. In this way the number of attempts
set in UVRep attempt are still available.
Menu PAR Description UM Type FB BIT Def Min Max Acc
15.31 4670 Optionbus activity ENUM Disable 0 2 ERW
Setting of the behaviour of the AFE product in case of an Opt Bus Fault [16] alarm.
0 Ignore
1 Warning
2 Disable
Menu PAR Description UM Type FB BIT Def Min Max Acc
15.32 4680 GroundFault thr perc FLOAT 10.0 0.0 150.0 ERWS
Setting of the threshold for the ground short circuit alarm Ground Fault [3].
Menu PAR Description UM Type FB BIT Def Min Max Acc
15.33 4700 Alarm dig sel 1 ENUM No alarm 0 40 ERW
15.34 4702 Alarm dig sel 2 ENUM No alarm 0 40 ERW
15.35 4704 Alarm dig sel 3 ENUM No alarm 0 40 ERW
15.36 4706 Alarm dig sel 4 ENUM No alarm 0 40 ERW
Setting of the alarm signal to enable on a digital output. The digital output is selected
using parameters Alm dig out mon 1÷4, which can be enabled in the L_DIGSEL1
selection list.
0 No alarm
1 Overvoltage
2 Undervoltage
3 Ground fault
4 Overcurrent
5 Desaturation
6 MultiUndervolt
7 MultiOvercurr
8 MultiDesat
9 Undervolt AC
10 Overvoltage AC
11 Heatsink OT
12 HeatsinkS OTUT
13 Intakeair OT
14 Drive overload
15 Bres overload
16 Opt Bus fault
17 Opt 1 IO fault
18 Opt 2 IO fault
19 Opt Enc fault