128 AFE200 • Instruction Manual
20 External fault
21 Emg stop alarm
22 Power down
23 Prc fbk loss
24 Not Used1
25 Not Used2
26 Not Used3
27 Not Used4
28 Not Used5
29 Not Used6
30 Not Used7
31 Not Used8
32 Not Used9
33 Plc1 fault
34 Plc2 fault
35 Plc3 fault
36 Plc4 fault
37 Plc5 fault
38 Plc6 fault
39 Plc7 fault
40 Plc8 fault
Menu PAR Description UM Type FB BIT Def Min Max Acc
15.37 4720 Alm autoreset time s FLOAT 0.0 0.0 60.0 ERW
Setting of the time interval that must pass before executing an automatic reset.
If no alarms are enabled the AFE product is set to restart.
If some alarms are still enabled the AFE product is set to execute a new attempt at
automatic reset.
At each attempted reset a counter increases. If the limit set in the PAR 4722 Alm
autoreset number parameter is reached the AFE product is set to make no more at-
tempts at reset and waits for a user reset.
The counter is set to zero when an automatic reset or user reset is performed and no
alarms are enabled.
If the parameter is 0 the function is disabled.
Menu PAR Description UM Type FB BIT Def Min Max Acc
15.38 4722 Alm autoreset number UINT16 20 0 100 ERW
Setting of the maximum number of attempted automatic resets.