AFE200 • Instruction Manual 61
Note ! In the procedures described below, the settings have been made using the AFE200-4450 drive.
Step 1 - Connections
Connect the power supply line and enabling contacts as shown in the diagram in
chapter 5.4.1.
Checks to be performed before powering the drive
Check that the supply voltage is correct and that the output terminals on the
drive (C, D) are connected correctly.
Check that all the drive control circuit terminals are connected correctly. Check
that all control inputs are open.
Powering the drive
After completing all the checks described above, power the drive and proceed
to Step 2.
Step 2 - Setting of the capacitor value
The factory setting for the AFE200 capacitor value is displayed. The capacitor
values of the drives connected to the DC BUS must be added to this (value of the
DC-link capacitors). This setting must not be higher than the maximum capacitor
value shown in table 10.4.
T+ T- EN LOC ILim n:0 AL
01 MONITOR
02 DRIVE INFO
03 STARTUP WIZARD
04 DRIVE CONFIG
T+ T- EN LOC ILim n:0 AL
STARTUP WIZARD
Set capacitor value ?
E=Yes Down=Next
E
T+ T- EN LOC ILim n:0 AL
S E Q . 0 1
PA R : 4 5 8
DC link ca
p
acitor
3400 uF
Def: 3400.0
T+ T- EN LOC ILim n:0 AL
1 3 . 0 1
PA R : 1 0 0
Rated voltage
+ V
Def: +400
000000400
E
T+ T- EN LOC ILim n:0 AL
S E Q . 0 1
PA R : 4 5 8
DC link ca
p
acitor
V
Def: 3400.0
0003400.0
T+ T- EN LOC ILim n:0 AL
S E Q . 0 1
PA R : 4 5 8
DC link ca
p
acitor
V
Def: 3400.0
0003400.1
E
E
At the end of the procedure, proceed to Step 3.
Step 3 - Setting of the choke value
The factory setting for the line choke is proposed as dened in chapter 11.2.1. To
change this value, type Enter and follow the instructions or press ▼ to go to step
4.
T+ T- EN LOC ILim n:0 AL
STARTUP WIZARD
Set induct. value ?
E=Yes Down=Next
E
T+ T- EN LOC ILim n:0 AL
S E Q . 0 1
PA R : 1 2 0
In
p
ut inductance
0.7150mH
Def: 0.7150
T+ T- EN LOC ILim n:0 AL
1 3 . 0 1
PA R : 1 0 0
Rated voltage
+ V
Def: +400
000000400
E
T+ T- EN LOC ILim n:0 AL
S E Q . 0 1
PA R : 1 2 0
In
p
ut inductance
mH
Def: 0.7150
0000.7150
T+ T- EN LOC ILim n:0 AL
S E Q . 0 1
PA R : 1 2 0
In
p
ut inductance
mH
Def: 0.7150
0000.7151
E
E
Step 4 - Setting of the DC-link parameter
The factory settings for the DC-link voltage (as a function of the mains voltage)
and acceleration and deceleration times are proposed in sequence. To change the
value type Enter and follow the instructions or press ▼ to go to the next step.