EasyManua.ls Logo

gefran AFE200 Series

gefran AFE200 Series
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AFE200 • Instruction Manual 67
The reactive current reference is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc
1.8 284 Active current A FLOAT 16/32 0.0 0.0 0.0 ER
The active current value currently in use is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc
1.9 286 Reactive current A FLOAT 16/32 0.0 0.0 0.0 ER
The reactive current value currently in use is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc
1.10 256 Phase U voltage V FLOAT 16/32 0.0 0.0 0.0 R
The phase U voltage is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc
1.11 258 Phase V voltage V FLOAT 16/32 0.0 0.0 0.0 R
The phase V voltage is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc
1.12 260 Phase W voltage V FLOAT 16/32 0.0 0.0 0.0 R
The phase W voltage is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc
1.13 248 Power factor FLOAT 0.0 0.0 0.0 ER
The power factor value (cosφ) is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc
1.14 262 Output power kW FLOAT 16/32 0.0 0.0 0.0 ER
The value of the power generated into the mains is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc
1.15 264 Output energy kWh FLOAT 0.0 0.0 0.0 ER
The value of the energy generated onto the mains is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc
1.16 368 Drive overload accum perc UINT16 16/32 0 0 100 ER
The drive overload level is displayed. An instantaneous overload of 180% of the drive
rated current is allowed for 0.5s. The thermal image I²t adjusts the drive output current
thresholds. During normal operation, the instantaneous output current value can reach
180% of the drive rated current. After 0.5s at 180%, the output current threshold is
reduced to 150%. When the overload level PAR 368 Drive overload accum reaches
100%, the output current threshold is reduced to 100% of the rated current, and stays
at that value until the I²t integrator cycle is complete. At this point the 180% instantane-
ous overload is re-enabled.

Table of Contents