74 AFE200 • Instruction Manual
4 - CONFIG DRIVE
Menu PAR Description UM Type FB BIT Def Min Max Acc
4.1 550 Save parameters BIT 0 0 1 RW
Any changes to parameter values immediately affect drive operations, but are not
automatically saved in the permanent memory.
The “Save Parameters” command is used to save current parameter values in the
permanent memory.
Any changes that are not saved will be lost when the drive is switched off.
To save parameters follow the procedure described in STEP 6 of the Startup wizard.
Menu PAR Description UM Type FB BIT Def Min Max Acc
4.2 554 Access mode ENUM Facile 0 1 RW
With this parameter you can restrict access to advanced conguration.
0 Easy
1 Expert
The Easy mode gives access to a list of parameters that can be used for rapid drive
commissioning. This type of conguration is suitable for the majority of applications.
Setting the parameter to Expert gives access to all the parameters in the rmware.
This mode allows an extremely high level of customization to be achieved in order to
exploit the potential of the AFE200 to the full.
Menu PAR Description UM Type FB BIT Def Min Max Acc
4.3 120 Input inductance mH FLOAT CALCF 0.0 0.0 RWZS
Setting of the input choke value. This is used to calculate the voltage and current
regulator gains.
Menu PAR Description UM Type FB BIT Def Min Max Acc
4.4 458 DC link capacitor uF FLOAT SIZE 0.0 0.0 RWZS
Setting of the value of the DC-link capacitors.
Menu PAR Description UM Type FB BIT Def Min Max Acc
4.5 2020 Take parameters BIT 0 0 1 RWZ
Stores the choke and capacitor settings. This command must be supplied last after
entering the appropriate values of all the parameters listed above. This involves cal-
culating the voltage and current regulator gains. The drive cannot be started until the
Take parameters command has been set.
Note! This is not saved permanently. Use the “Save Parameters” command in the DRIVE CONFIG menu to
save in the permanent memory.
Menu PAR Description UM Type FB BIT Def Min Max Acc
4.6 2028 Take status ENUM Required 0 0 R
Indication of the status of parameter saving.