AFE200 • Instruction Manual 75
0 Required
1 Done
The parameter displays the Required message when the motor parameters that have
been entered need to be saved. When they have been saved the parameter indicates
Done.
Menu PAR Description UM Type FB BIT Def Min Max Acc
4.7 558 Application select ENUM None 0 2 ERWZ
Selection of which IEC 61131-3-compliant application to make operational.
0 None
1 Application 1
2 Application 2
Note! The Load Default command (par. 580) does not modify this parameter
.
Menu PAR Description UM Type FB BIT Def Min Max Acc
4.8 560 Mains voltage ENUM 400 V SIZE SIZE ERWZS
Setting of the available mains voltage value in Volts. Detection of the undervoltage
alarm refers to this value.
0 320 V
1 270 V
2 290 V
3 230 V
4 380V
5 400 V
6 415 V
7 440 V
8 460 V
9 480 V
10 500 V
11 575 V
12 690 V
Menu PAR Description UM Type FB BIT Def Min Max Acc
4.9 552 Mains frequency ENUM 50 Hz 0 1 ERWZS
Setting of the value of the available mains frequency in Hz.
0 50 Hz
1 60 Hz
Menu PAR Description UM Type FB BIT Def Min Max Acc
4.10 562 Switching frequency ENUM SIZE SIZE SIZE ERWS
Setting of the switching frequency value in kHz. The maximum value that can be set
depends on the size of the drive.
0 1 kHz
1 2 kHz
2 3 kHz
3 4 kHz
4 6 kHz