92 AFE200 • Instruction Manual
AnInp Drive
AnInp Terminal
100%
-100%
10V
-10V
100%
-100%
Par.1522=50%
Par.1522=50%
Menu PAR Description UM Type FB BIT Def Min Max Acc
9.13 1524 An inp 1 alt value cnt INT16 16/32 0 -16384 16384 ERW
9.29 1574 An inp 2 alt value cnt INT16 16/32 0 -16384 16384 ERW
Setting of a xed alternative value for the relative analog input, which can be selected
via a command enabled by a digital input programmed with the An inp alt sel src
parameter.
Menu PAR Description UM Type FB BIT Def Min Max Acc
9.14 1526 An inp 1 sign src LINK 16 6000 0 16384 ERW
9.30 1576 An inp 2 sign src LINK 16 6000 0 16384 ERW
L�DIGSEL2
Selection of the origin (source) of the signal to be assigned to the relative digital input
for selecting the direction of rotation of the motor. The functions that can be associated
with the digital outputs are listed in the “L_DIGSEL2” selection list.
Menu PAR Description UM Type FB BIT Def Min Max Acc
9.15 1528 An inp 1 alt sel src LINK 16 6000 0 16384 ERW
9.31 1578 An inp 2 alt sel src LINK 16 6000 0 16384 ERW
L�DIGSEL2
Selection of the origin (source) of the signal to be assigned to the relative digital input
for selecting the alternative analog reference. The functions that can be associated
with the digital outputs are listed in the “L_DIGSEL2” selection list.
Menu PAR Description UM Type FB BIT Def Min Max Acc
9.16 1532 Analog input 1 dest ILINK 0 0 0 ER
9.32 1582 Analog input 2 dest ILINK 0 0 0 ER
The function for which the relative analog input has been programmed and on which it
acts is displayed.