AFE200 • Instruction Manual 93
Menu PAR Description UM Type FB BIT Def Min Max Acc
9.33 1600 Analog input 1X mon cnt INT16 16/32 0 0 0 R
9.44 1650 Analog input 2X mon cnt INT16 16/32 0 0 0 R
The value of the voltage output of the function block of the relative analog input is
displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc
9.34 1602 Analog inp 1X type ENUM -10V..+10V 0 2 RW
9.45 1652 Analog inp 2X type ENUM -10V..+10V 0 2 RW
Selection of the type of expansion card input (voltage or current input). Depending on
the input signal, move the switches on the regulation card. Standard inputs are coded
for voltage signals.
0 -10V..+10V
1 0.20mA ... 0.10V
2 4..20mA
Select option 0 in order to connect a maximum voltage of ±12.5V (typically ±10V/5mA)
to the analog input concerned. If the signal is used as a reference, reverse the direc-
tion of rotation of the drive by inverting the voltage polarity.
Select option 1 to connect a max voltage of 12.5V (typically 10V/5mA) or a signal in
current from 0 ... 20 mA to the analog input concerned. The signal must be positive.
Select option 2 to connect a current signal of 4...20 mA to the analog input concerned.
The signal must be positive.
Menu PAR Description UM Type FB BIT Def Min Max Acc
9.35 1604 Analog inp 1X scale FLOAT 1.0 -10.0 10.0 RW
9.46 1654 Analog inp 2X scale FLOAT 1.0 -10.0 10.0 RW
Setting of a multiplier factor to apply to the relative analog input of the expansion card.
Example :
1
2
1
2
Analog inp xX scale = 1,0
Analog inp xX scale = 2,0
0
10V
100%
50%
5V
Speed
The speed reference of a drive is assigned with a max external voltage of 5V.
As the Analog inp X scale parameter the scale factor of 2 is entered (10V : 5V).

Table of Contents