98 AFE200 • Instruction Manual
1500 Analog input 1 mon
10V = 10V Analog input
1550 Analog input 2 mon
1600 Analog input 1X mon
1650 Analog input 2X mon
368 Drive overload accum 5V = 100% Accumulator
4024 … 4174 Fieldbus M->SX mon
10V = 16384 * 2^16
3700 … 3730 Pad X
Menu PAR Description UM Type FB BIT Def Min Max Acc
10.1 1800 Analog out 1 src LINK 16/32 6000 0 16384 RW
10.2 1802 Analog out 2 src LINK 16/32 6000 0 16384 RW
L�ANOUT
Selection of the origin (source) of the signals that can be placed as variables on the
analog outputs. The functions that can be assigned to the analog outputs are listed in
the “L_ANOUT” selection list.
Menu PAR Description UM Type FB BIT Def Min Max Acc
10.3 1808 Analog out 1 scale FLOAT 1.0 -10.0 10.0 RW
10.4 1810 Analog out 2 scale FLOAT 1.0 -10.0 10.0 RW
Parameter for setting a multiplier factor of the signal of the relative analog output. It
can be used to amplify or reduce the input value of the relative analog output block.
1
2
3
+10V
-10V
0V
Internal V
1
2
3
Par. 1808 (1810) = 1
Par. 1808 (1810) = 0,5
Par. 1808 (1810) = -1
Stp Var x par. 1808 (1810)
Vout = 10 x ( )
FS Var
where:
Vout output voltage on the card terminals.
Stp Var actual value of the variable (variable unit)
FS Var full scale of the variable (variable unit)