10 AGL50-EV
BU-Off In use (Vdc) = BU-Off (Vdc) * P.344 / 100
If P.344 = 90 that the thresholds in use are:
Mains Voltage Vdc Nominal BU-On In Use BU-Off In Use
(Vac) (Vdc) (Vdc) (Vdc)
380 535 702 693
400 564 702 693
420 592 702 693
440 620 702 693
460 648 702 693
480 676 702 693
3.6 Open-Loop and Closed-Loop control section
No. 1 Programmable Analog input: ��������� Analog input 1 = -10...+10 V 0.5 mA max, 10 bit + sign / unipolar or bipolar
No. 1 Programmable Analog output: ������� 0 ... 10 V / 5 mA max
Analog output 1 = 0...+10V, 10 bit, Frequency output absolute value (default)
No. 6 Programmable Digital inputs: �������� 0...24V / 5 mA
Digital input 6 = Freq Sel 3 src (default)
Digital input 5 = Freq Sel 2 src (default)
Digital input 4 = Freq Sel 1 src (default)
Digital input 3 = Run Rev src (default)
Digital input 2 = Run Fwd src (default)
Digital input 1 = Enable src (default)
No. 1 Programmable Digital output: �������� Digital outputs 1 = Drive Ready (default)
No. 2 Programmable Relais Digital outputs: �� Relay Digital outputs 1 = Brake cont (default)
Relay Digital outputs 2 = Not in alarm (default)
Note!
Dig. out. 1 > open collector type: 30V / 40mA
Relais Dig. out. 1 and 2 > relay output type: 230Vac-2A / 30Vdc-2A
Internal voltage supply: ������������������ + 21Vdc (±3 %), 75mA (Terminal 28)
024V (Terminal 26)
+ 10Vdc (±3 %), 10mA (Terminal 7)
- 10Vdc (±3 %), 10mA (Terminal 9)
3.7 Accuracy
Reference value ����������������������� 0.1 Hz (Resolution of Reference preset via terminals)
0.1 Hz (Resolution of Reference preset via interface)