38 AGL50-EV
7.6 Timer 1 function (from fw 03.07)
The timer function allows to apply delays and pulses to an input signal selected from a pick list.
Timer 1
Timer1out
Timer1set src
Timer 1 mode
Timer1delay
Off
On delay
Off delay
On/Off delay
Pulse
Sym flasher
Menu A - APPLICATION
Cod. Display (Description) Def. Min. Max
A.320 Timer 1 mode 0 0 5
Select working mode of Timer 1
[0] Disable
[1] On delay
[2] Off delay
[3] On/Off delay
[4] Pulse
[5] Sym asher
[0] Disable Output is always 0ff
Timer 1in
Timer 1 out
On delay
Tt<T
T=Timer 1 delay
Timer 1in
Timer 1 out
Off delay
T T
T
T=Timer 1 delay
[1] On delay The closure of the Input (On) is transferred on Output after pre-set time has elapsed.
[2] Off delay The closure of the Input (On) is transferred immediately on the Output.
The opening of the Input (Off) initiates the pre-set delay, after which the Output is reset (Off).